Once I needed to create a template in Zabbix to monitor Netman 102 plus, I will describe which SNMP OIDs I used.
To connect to Netman 102 plus, the default login is root and the password is password, the IP address is assigned via DHCP, if something is not configured correctly, then there is a reset button.
Incoming parameters:
upsInputVoltage
1.3.6.1.2.1.33.1.3.3.1.3
upsInputFrequency (*0.1)
1.3.6.1.2.1.33.1.3.3.1.2
Number of Input Lines
SNMPv2-SMI::mib-2.33.1.3.2.0
Input Line X Index
SNMPv2-SMI::mib-2.33.1.3.3.1.1
Outgoing parameters:
upsOutputVoltage
1.3.6.1.2.1.33.1.4.4.1.2
upsOutputPower
1.3.6.1.2.1.33.1.4.4.1.4
upsOutputFrequency (*0.1)
1.3.6.1.2.1.33.1.4.2
upsOutputPercentLoad
1.3.6.1.2.1.33.1.4.4.1.5
upsOutputSource
1.3.6.1.2.1.33.1.4.1
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7)
Battery information:
upsBatteryVoltage (*0.1)
SNMPv2-SMI::mib-2.33.1.2.5.0
BatteryChargeRemainingPercent
SNMPv2-SMI::mib-2.33.1.2.4.0
BatteryRuntimeRemainingInMinutes
SNMPv2-SMI::mib-2.33.1.2.3.0
upsSecondsOnBattery
1.3.6.1.2.1.33.1.2.2.0
upsBatteryStatus, 2 = Normal
1.3.6.1.2.1.33.1.2.1
Battery Temperature (C)
1.3.6.1.2.1.33.1.2.7
upsIdentModel
1.3.6.1.2.1.33.1.1
upsIdentUPSSoftwareVersion
1.3.6.1.2.1.33.1.1.3
Alarm present (1 = true, 0 = false)
SNMPv2-SMI::mib-2.33.1.6.1.0