Setting up ETP4830 A1 with Huawei OLT

For example, I will take the ETP4830 A1 power supply at 48V 15A (there is a model for 30A) and connect it to the MA5608T so that I can monitor the percentage of battery charge, set the correct parameters for charging batteries (default 53.5V floating and 56.5V accelerated) their capacity (the default is 40Ah or 65Ah), etc.

I ordered these blocks on Alibaba with delivery via Meest China.

To connect, I did not use a standard ethernet patch cord, but with such a pinout, the first column for MCUD1 in the OLT is a regular crimp for ethernet, the second for SMU01C or a similar module, for example PMU11A, EPMU03:

1 (white-orange)7 (white-brown)
2 (orange)8 (brown)
3 (white-green)
4 (blue)1 (white-orange)
5 (white-blue)2 (orange)
6 (green)4 (blue)
7 (white-brown)
8 (brown)

The ETP4830 A1 (SMU01C) has a default flow rate of 9600 and address 0, if it is different on the OLT, then you can set 19200 using the buttons through the display on the SMU01C (default password is 000001) or execute the command on the OLT:

emu baudrate 9600

Add emu:

emu add 2 smu 0 0 "SMU01C"

Let’s see the status:

display emu 2

EMU ID: 2
  ----------------------------------------------------------------------------
  EMU name    : SMU01C
  EMU type    : SMU
  Used or not : Used
  EMU state   : normal
  Frame ID    : 0
  Subnode     : 0
  ----------------------------------------------------------------------------

If everything is OK, the status is “normal” and not “fault”, then let’s move on to managing the added emu:

interface emu 2

Let’s see the current settings:

display power environment parameter
display power system parameter

EMU ID: 2                           Power system information
  ----------------------------------------------------------------------------
  Charge control state: Automatic control
  Equalizing voltage  : 56.50V      Floating voltage      : 53.50V
  Charge Lmt quotiety : 0.15        Equalizing time       : 60 days
  Battery number      : 1           Battery 0 capacity    : 65  AH
  Batt_temp_test_upper: 80 C        Batt_temp_test_lower  : -20C
  Batt_temp_Alam_upper: 50 C        Batt_temp_Alam_lower  : -15C
  Temp redeem quotiety: 80mV
  AC over alarm voltage : 280V      AC lack alarm voltage : 180V
  DC over alarm voltage : 58 V      DC lack alarm voltage : 45 V
  Power module number : 0
  Battery high-temperature-off permit     : Permit
  Battery high-temperature-off temperature: 53 C
  Battery-lack-voltage-off-permit  : Permit
  Battery-lack-voltage-off voltage : 43.00V
  Battery barcode : -
  ----------------------------------------------------------------------------
display power alarm

EMU ID: 2                           Power alarm information
  ----------------------------------------------------------------------------
  AC supply yes    : Yes               AC supply lack : Normal
  DC voltage lack  : Normal
  Load fuse        : Connect
  Battery-high-temperature-off : On    Battery-lack-voltage-off : On
  Battery loop     : Connect
  Battery Temperature alarm : Normal
  Module 0         : Normal
  Module 1         : Normal
  Door alarm       : Alarm          Water alarm       : Normal
  Smoke alarm      : Normal         Wiring alarm      : Normal
  Environment Temperature       : Normal  Environment Humidity       : Normal
  Battery Dectect               : Normal
  Battery 1 Temp-Sensor         : Invalid Environment 1 Temp-Sensor  : Invalid
  Environment Humidity-Sensor   : Invalid
  ----------------------------------------------------------------------------
  DigitalID Name                  State |DigitalID Name                  State
  Spare Dig0                      Normal|Spare Dig1                      Normal
  Spare Dig2                      Normal|Spare Dig3                      Normal
  Spare Dig4                      Normal|Spare Dig5                      Normal
  Spare Dig6                      Normal
  ----------------------------------------------------------------------------

An example of changing parameters, with a question mark, let’s see which parameter needs to be specified, since the order of specifying parameters on different devices is different:

power battery parameter ?
power battery parameter 1 0.10 60 65

Battery group num, default 1 (0-2) (0 – if batteries are disconnected)
Power battery charge limit quotiety, default 0.15 (0.05-0.25)
Equalizing charge time, default 60 days (30-240)
Battery group 0 capacity, default 65, unit is AH (5-1000)

If the batteries are less than 65Ah, then we will indicate the correct capacity and the correct charge factor, otherwise they will be charged with a large current and may swell after a while. For example, multiply the capacity by the charge factor and get the charge current: 100Ah*0.10=10A. It is advisable not to exceed a tenth, for example, for a capacity of 65Ah, the charge current is a maximum of 6.5A, if you specify less, then the batteries will take longer to charge.

An example of setting voltage and battery charging mode, humidity and temperature alarms:

power charge ?
power environment humidity ?
power environment temperature ?

Specify the date of installation of the batteries:

power batteryinstall 2023-03-10
display power batteryinstalltime

Battery test parameters:

power battery-test ?
power battery-test simply-test start
display power battery-test info all
display power battery-test parameter

EMU ID: 2                           Battery test configuration parameter
  ----------------------------------------------------------------------------
  Discharge test         : auto-test forbid
  Normal Test End-Voltage: 45.6 V
  Normal Test Duration   : 10 Hours
  Simply Test End-Voltage: 45.0 V
  Simply Test Duration   : 60 Minutes
  Test phase             : Discharge complete
  Battery alarm-threshold: 70 %
  ----------------------------------------------------------------------------

Exit the configuration mode and save the configuration:

quit
save

If you connect Lifepo4 batteries, you can use the buttons on the display to indicate Battery-lack-voltage-off 47.8, Load off 47.9, and for example floating 55.0 and equalizing (fast charging) voltage 55.5, depending on the battery characteristics. I specified the charging current for a 50A battery as 15A (in the settings I specified 0.25*60A), I note that the factory battery fuse is set to 20A.