SNMP MIB/OID for Huawei ETP4830

Let’s say a Huawei ETP4830 power supply unit (UPS) or a similar model is connected to the Huawei OLT MA5600 series, now I will show several SNMP OIDs with which I took data on voltage and battery charge:

AC input voltage (multiply the result by 0.001):

1.3.6.1.4.1.2011.6.2.1.2.1.3

Output voltage of module 1 and module 2 (multiply the result by 0.001):

1.3.6.1.4.1.2011.6.2.1.5.1.4

Battery charge in %:

1.3.6.1.4.1.2011.6.2.1.6.1.1.2

Voltage settings for battery charging:

1.3.6.1.4.1.2011.6.2.1.3

Values from temperature sensors °C:

1.3.6.1.4.1.2011.6.1.1.2.1.9

You can check SNMP OID for example from Linux:

snmpwalk -v2c -c community ixnfo.com OID

See also my articles:
Connecting and configuring EPS30-4815AF with Huawei MA5600
Other articles

Download

Leave a comment

Leave a Reply